Flange gate model F0211-300 ( for vertical indicator)
Manually operated wedge gate valve with non-rising stem. The designs allows an indicator to be fitted to show the wedge position of the gate valve.
Application
Manually operated wedge gate valve with a non-rising stem. The design allows the assembly of an indicator showing the position of the wedhe of the gat. An optional kit can be fitted to the gate valve indicator to monitor the position of the gate valve (fully open or fully closed). Installed in pumping stations, at the branches of installations, outside buildings in the ground, as a shut-off gate valve at external hydrants.
Consult the technical department for available versions and scope of approvals and certificates.Design and materials are subject to change without prior notice.
Technical data
Available siezes: DN 50 – DN300 (2” – 12”) 1
Connection: flanged according PN-EN 1092 PN10/16 2
Working pressure: 20,7 bar (300 psi)
Medium: water and other inert liquids
Operating temperature: – 10°C to +82°C
Finish: external and internal epoxy-coating (FBE) according to AWWA C550
* Gates valves DN65 – DN80 (2½” – 3”) prepared for vertical mounting of the indicator possible on request
** Other flange drillings also possible.
Accessories: horizontal gate valve position indicator model F0600-WP or F0800-WP
veritcal gate valve position indicator modelF0600-IP or F0800-IP
limit switch prepared for monitoring the position of the gate valve wedge (mounting on the position indicator).
Design and assembly
- Full flow desing according to AWWA C515
- Installation lenght according to ASTM B16.10 and EN558 series 3
- non-lifting system
- triple O-ring stem seal
- additional threaded hole (NPT) in body
- available in different pressure classes
- can be supplied without indicator flange
- Stem may be manufactured from ASTM B150 bronze or other meterial
- the stem can be made of stainless steel ASTM A276 grade 316
- when gates valves are installed on horizontal pipelines, the stem should be positioned vertically
- when gate are installed on vertical pipelines, the stem shall be positioned horizontally